SF160M

MCG SURGE PROTECTION

STANDARD CLASS

BUILDING ENTRY PROTECTOR
Ipeak = 160kA




Easy Installation  <30 min.

- Mount Pre-tested SF160M
- Connect Micro-Z Cable to panel

- Apply power - system is protected!

10-Year Warranty

Free modules for life

ulbal1i1.gif (1059 bytes)

UL 1449
2nd Edition Listed

ANSI/IEEE C62.41-1991
CATEGORY C

SF160M.jpg
DESCRIPTION FEATURES
The SF160M offers superb protection at the main service panel for most applications. Computers, sensitive business equipment and other high tech equipment are guarded from damage, errors and downtime resulting from high speed transients.

The SF160M system provides a better transient pathway to ground. The SF160M system consists of a low impedance cable having only 1/3 the voltage drop of conventional cabling and a protector design with a very low internal voltage drop. This results in a lower transient  exposure to sensitive downstream equipment. The plug-in, plug-out protection modules guarantee a quick and easy repair in the unlikely event of a catastrophic transient occurrence, such as a nearby lightning strike.

The on-board diagnostics include front panel and internal LEDs, transient event counter, audible alarm and remote alarm. In addition, the unit is housed in a rugged indoor/outdoor NEMA 4 enclosure.

SF160M Data Sheets SF160M DATA SHEETS
SF160M Engineering Specifications SF160M ENGINEERING SPECIFICATIONS

SF160M INSTALLATION INSTRUCTIONS SF160M(Y & T) INSTALLATIONS SHEETS
SF160M INSTALLATION INSTRUCTIONS SF160M(DELTA) INSTALLATIONS SHEETS
Free Adobe Acrobat Reader

  • Ipeak of 160,000  Amps per phase - major surge current diversion
  • Built-in redundancy - dual-level protection for dependable performance.
  • All modes protected, L-N, L-G, L-L, N-G.
  • Patented "low impedance" MICRO-Z design.
  • Large cross-sectional copper conductors.
  • MICRO-Z cable provided at no cost.
  • Continuous on-line status monitoring.
  • Diagnostics - pinpoints the problem location.
  • Remote status monitoring capability.
  • Personnel safety -  integrated power disconnect with LEXAN dead-front construction.  Only MCG has it!
  • Warranty - 10 year on Protector and a lifetime replacement of modules without charge.

CONFIGURATIONS:

MODEL RATED VOLTAGE DESCRIPTION

ENERGY ABSORPTION
(8/20µs)
JOULES TOTAL

UL1449
SURGE VOLTAGE
(8/20us)
500A

SF160M-120T 120/240V 1Ø, 3W+GND 8,772 400
SF160M-120Y 120/208V 3Ø, 4W+GND, WYE 8,772 400
SF160M-220Y 220/380V 3Ø, 4W+GND, WYE 23,520 700
SF160M-240Y 240/415V 3Ø, 4W+GND, WYE 23,520 700
SF160M-240D 240V 3Ø, 3W+GND, DELTA 20,160 700
SF160M-240DCT 240/120/120V 3Ø, 4W+GND, HI-LEG 15,064 700/400
SF160M-277Y 277/480V 3Ø, 4W+GND, WYE 25,200 800
SF160M-480D 480V 3Ø, 3W+GND, DELTA 36,000 1500

ELECTRICAL SPECIFICATIONS

MAX. CONTINUOUS OPERATING VAC:   115%
RESPONSE TIME:    <5 NANOSECONDS
MODES OF PROTECTION:    L-N, L-G, L-L, N-G (where applicable)
SURGE CURRENT/PHASE:    160kA (8/20µs) - 1 EVENT
SURGE LIFE/PHASE:        6kA (8/20µs) - 10,000 IMPULSES 
FILTER ATTENUATION MIL STD (220A50ohm):   120VAC 240VAC 277VAC 480VAC
-30db     100kHz 25kHz 80kHz 80kHz
-40db     200kHz 100kHz 180kHz 180kHz
-50db     280kHz 180kHz 210kHz 250kHz
-55db     310kHz 200kHz 390kHz 390kHz
PROTECTION PRESENT INDICATORS:    GREEN LED
REDUCED PROTECTION INDICATOR:    RED LED
ADDITIONAL STATUS INDICATORS:    AUDIBLE ALARM, EVENT COUNTER, REMOTE DRY CONTACTS
OPERATING ALTITUDE:    13,000 ft. (4000m)
TEMPERATURE (OPERATING/STORAGE):    -40° to +70°C/-40° to +85°C
ENCLOSURE:    NEMA 4, 14 GAUGE STEEL
DIMENSIONS:    12" x 10" x 5"
MOUNTING:    12.75" x 8"/.3125 ID - 4 HOLES
CABLE CONNECTION:    MICRO-Z CABLE SUPPLIED FREE (#10 AWG)
SHIPPING WEIGHT:    23 lbs.